690 Specifications
|
|
|
INPUT
|
| Supply Voltage |
690Vac |
| Supply Phases |
3 phase, 3 wire, earthed neutral |
| Supply Tolerance |
-20% to +5% |
|
Frequency Range |
50(60Hz option) |
| Current |
£ Output Current |
| Displacement Factor |
³ 0.95 |
| Distortion Factor |
£
0.88 |
| Power Loss Ride Through |
> 2 seconds at rated voltage |
|
OUTPUT
|
| Voltage |
0 to Vin |
| Frequency Range |
0 - 100Hz |
| Efficiency (at rated load) |
>97% @ 2kHz switching
>96% @ 4kHz switching |
| Control Method |
Vectorque (True Sensorless
Vector) |
| Current Overload Capacity Rated Models: |
150% for 30 secs @ 50oC/2kHz;
40oC/4kHz
125% for 30 secs @ 40oC/2kHz;
30oC/4kHz |
|
ENVIRONMENTAL
|
| Protection Standard |
IP20 |
| Operating Temperature |
0°C - 50°C |
|
Temperature Re-rating
of
output current
|
120% @ 40oC/2kHz or 30oC/4kHz |
| Altitude |
1000m |
| Altitude De-rating (>1000m) |
-1 per 100m; 3000m max. |
| Relative Humidity |
<90%, non-condensing |
|
DRIVE
/ MOTOR PROTECTION
|
| Inverter |
thermal, voltage & short circuit |
| Motor |
500V/µs dV/dt filter, thermal
protection, ground fault, phase loss, motor PTC |
|
CONTROL
|
| Control Method |
Vectorque (True Sensorless
Vector) |
| Analogue Inputs |
2 inputs, configurable as
+10Vdc,
4 - 20mA |
|
Digital Inputs
|
6 configurable inputs plus 1 PTC or trip input
|
|
Analogue Outputs
|
2 outputs configurable as + 10Vdc,
4 - 20mA
|
|
Digital Outputs
|
2 High Speed Open Collector
|
|
Relay Outputs
|
3 configurable change over relays, 230Vac or 24 Vdc, 1 Amp non-inductive
|
|
SERIAL
COMMUNICATION OPTIONS
|
| Standard |
RS232 |
| Optional |
Isolated RS485, Device Net,
Profibus – DP, Modbus, Modbus plus, Interbus, Remote I/O |
|
ELECTROMAGNETIC COMPATIBILITY |
|
The Microdrive V Series complies with the following EMC standards: EN61800-3; 1996 (Adjustable speed electrical power drive systems).
The Micordrive V Series is CE and C-tick certified. |
Model Selection Guide
|
|
|
|
| Model |
Output Current
@50 C, 2kHz
(150% O/L)*
|
Output Current
@40 C, 2kHz
(125% O/L)*
|
Overload Current
|
Typical Motor Rating**
(150% O/L)
|
Typical Motor Rating**
(125% O/L)
|
| MV100E20 |
100A
|
120A
|
150A
|
90KW
|
110KW
|
| MV167E20 |
167A
|
200A
|
250A
|
160KW
|
200KW
|
| MV200E20 |
200A
|
240A
|
300A
|
200KW
|
250KW
|
| MV300E20 |
300A
|
360A
|
450A
|
250KW
|
315KW
|
| MV400E20 |
400A
|
480A
|
600A
|
400KW
|
500KW
|
| MV500E20 |
500A
|
600A
|
750A
|
500KW
|
560KW
|
| MV600E20 |
600A
|
720A
|
900A
|
560KW
|
630KW
|
*2kHz switching frequency @610: SWFREQ = LOW
** Typical value only: Refer to motor numeplate current and compare with drive rated current.
Dimesions
|
Model
|
Height
(mm)
|
Width
(mm)
|
Cut out
(mm)
|
Depth
(mm)
|
Weight
(kg)
|
Gland Plate Width
(kg)
|
Airflow m3/min
|
Power Loss kW*
|
| MV100E20 |
1260 |
248 |
218 |
440 |
85
|
198
|
6
|
3.4
|
| MV167E20 |
1260 |
488 |
458 |
440 |
170
|
438
|
18
|
5
|
| MV200E20 |
1260 |
488 |
458 |
440 |
170
|
438
|
18
|
6
|
| MV300E20 |
1260 |
728 |
698 |
440 |
255
|
678
|
24
|
9
|
| MV400E20 |
1260 |
968 |
938 |
440 |
340
|
918
|
30
|
12
|
| MV500E20 |
1260 |
1208 |
1178 |
440 |
425
|
1158
|
36
|
15
|
| MV600E20 |
1260 |
1448 |
1418 |
440 |
510
|
1398
|
42
|
18
|
* Power loss at 50C rated current
|
|