500V Specifications |
400V Specifications |
| INPUT |
| Input supply voltages |
208 to 230Vac or 440 to
500Vac |
| Input supply phases |
3 phase, 3 wire, earthed neutral |
| Input supply tolerance |
-10% to +10% |
| Input frequency range |
48 to 62Hz |
| Input current |
< output current |
| Input displacement factor |
> 0.99 |
| Input current THD |
< 40% |
| Power loss ride through |
> 2 seconds at rated voltage |
| OUTPUT |
| Output voltage to motor |
0 to Vin -3V @ 100% load |
| Current overload capability |
CT: 150% for 30 secs at 50°C
150% for 60 secs at 40°C
VT: 120% for 60 secs at 40°C
|
| Frequency range |
0 to ±400Hz (max) |
| Efficiency (full load, 50Hz) |
> 97% |
| Suit motor rated voltages |
5 to 500Vac |
| Suit motor rated frequencies |
10 to 400Hz |
| Modulation method |
Space Vector modulation |
| Modulation frequency |
Up to 16kHz Whisper Wave or Narrow Band |
| ENVIRONMENTAL |
| Protection standard |
Enclosure, IP54/NEMA 12 |
| Operating temperature |
0°C to 50°C |
| Storage temperature |
-25°C to +80°C |
| Relative humidity |
< 90%, noncondensing |
| Altitude |
1000m |
| Altitude derating (>1000m) |
-1% per 100m; 3000m max. |
| DRIVE PROTECTION |
| Supply loss |
Input phase loss |
| Software thermal model |
Heatsink overheat |
| IGBT overload |
Internal air overheat |
| Output current limit |
Output current trip |
| DC bus voltage limiting |
|
| Short circuited load |
Ground fault |
| Low DC bus voltage |
Regeneration limit |
| Hardware failure |
|
| MOTOR AND DYNAMIC BRAKE PROTECTION |
| Motor thermal model trip |
PTC thermistor trip |
| Overload warning |
Shear pin trip (configurable) |
| Dynamic brake resistor thermal model trip |
| Torque limit and time-out (configurable) |
| Speed limit and time-out (configurable) |
|
CONTROL
|
| Control method |
Flux vector or V/Hz control |
| Analogue inputs |
2 inputs, configurable as 0-10 Vdc, ±10Vdc, 4-20mA or 0-20mA |
| Digital inputs |
6 configurable inputs plus 1 PTC or trip input |
| Analogue outputs |
2 outputs, configurable as 0-10Vdc, ±10Vdc, 4-20mA or 0-20mA |
| Relay outputs |
1 changeover, 2 normally open, rated 250Vac or 30Vdc, 2A non-inductive. |

|
DIMENSIONS
|
| Item Reference |
H mm (ins) |
W mm (ins) |
D mm (ins) |
Weight kg (lbs) |
| ME002D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME006D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME009D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME011D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME016D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME021D54 |
430 (16.9) |
139 (5.5) |
262 (10.3) |
10-14 (22-31) |
| ME030D54 |
430 (16.9) |
279 (11) |
262 (10.3) |
27 (59.5) |
| ME035D54 |
430 (16.9) |
279 (11) |
262 (10.3) |
27 (59.5) |
| ME041D54 |
430 (16.9) |
279 (11) |
262 (10.3) |
27 (59.5) |
Model Selection Guide
|
|